TABmaster Airflow Capture Hood Model 6720
Advanced capture hood with detachable Bluetooth micromanometer for direct volume flow plus pitot, velocity-grid and pressure measurements.
Products
| Model | Group | Positioning | Core fit |
|---|---|---|---|
| 6720 | Advanced capture hood | Direct terminal flow plus standalone pressure and velocity functions | HVAC/TAB, commissioning and critical-environment verification |
Key Features
Detachable micromanometer
Use the meter on the hood or independently with pitot tubes and velocity grids.
Bluetooth workflow
Supported mobile applications enable remote control and data recording.
Broad measurement set
Measures volume flow, differential pressure, calculated velocity, temperature and humidity.
Eight-thousand-record memory
Organize extended projects and export results for reporting.
Technical Specifications
| Parameter | Unit | Value / Description |
|---|---|---|
| CAPTURE HOOD | ||
| Airflow range | m³/h | 40–4,300 |
| Airflow accuracy | — | ±3% of reading ±8 m³/h above 85 m³/h |
| Standard hood | mm | 610 × 610 |
| Available hoods | — | Six configurations |
| DETACHABLE MICROMANOMETER | ||
| Pitot velocity range | m/s | 0.15–40 |
| Velocity-grid range | m/s | 0.15–15 |
| Differential-pressure range | Pa | −2,500 to 2,500 |
| Interfaces | — | USB and Bluetooth |
| GENERAL | ||
| Data memory | measurements | Up to 8,000 |
| Power | — | 4 × AA batteries or AC adapter |
| Weight | kg | Approx. 3.6 with standard hood |
Values shown are manufacturer specifications or documented configuration details. Confirm final model, probe, accessories, regional availability and calibration scope before ordering.
Applications
Terminal airflow balancing
Measure supply and return volumes directly at outlets.
Pitot-tube traverse
Detach the meter for in-duct velocity and flow calculation.
Pressure verification
Measure room and barrier pressure differentials.
Velocity-grid measurement
Use a grid for average face velocity at openings and filter banks.